EP3300 TLV series off grid solar system inverter


Features
• Pure sine wave output, split phase HOT1+ N + HOT2 available, 120VAC/220VAC
• MFD (multi-function display) & Friendly user interface
• 3 Steps optimizing charge for battery pack
• Overload and short-circuit protection
• Settable: charging/charging current, utility/Battery priority, utility input wide/
• narrow range
• Inverter voltage can be set to 100V/110V/120V
• Inverter frequency can be set to 50/60Hz
PRODUCT FEATURES
—— Smart & Intelligent Features ——
Pure sine wave output
Two pure sine wave AC 110V/120V output(Split Phase)

Smart Battery Chargers - 3 steps optimizing battery charge
Boost CC Stage: If A/C input is applied, the charger will run at full current in CC mode until the charger reaches the boost voltage.
Boost CV Stage: the charger will keep the boost voltage in Boost CV mode until the charge current less 6A continue 1minute or keep the boost voltage time more than 2hours. Then drop the voltage down to the float voltage.
Float Stage: In float mode, the voltage will stay at the float voltage. If the A/C is reconnected , the charger will reset the cycle above.

Easy to read all working modes and parameters in LCD
Line Mode
Input power will provide energy to load directly. And it will charge the battery at the same time. If voltage of input power is outside of section, the machine will switch to battery mode.

Battery Mode
The unit will get energy from battery and provide to load.

Fault Mode
If any fault has happened, the machine will enter to the mode. And fault code is displayed on the LCD.

Smart setting to make inverter work more efficiency
A: save mode switch to save more power:

B: Power Source - Battery/ AC Priority Setting:

UTI, utility priority (default); SBU, battery priority; Setting as below:

PRODUCT DETAILS
—— Must help you control every detail ——
① Switch on/off
② Page up
③ Menu
④ AC Status LED
⑤ Inverter Status LED
⑥ LCD Setting
⑦ Fault Warning LED
⑧ Enter and confirm
⑨ Page down
⑩ Battery -/+
⑪ BTS
⑫ AGS
⑬ Remote Panel
⑭ USB
⑮ Fan
⑯ AC Input Protect



① AC OUTPUT:
HOT1 - HOT2 240VAC/220 VAC/230VAC
② AC OUTPUT1:
HOT1 - N 120VAC/110 VAC/115VAC
③ AC OUTPUT2:
HOT2 - N 120VAC/110 VAC/115VAC
④ AC INPUT:
HOT1 - HOT2 240VAC/220 VAC/230VAC
⑤ 5.15A MAX JFCI Output
110V/115V/120V Socket, 15A MAX

PRODUCT SYSTEM CONNECTION
—— Inverter + Solar Charge Controller + Battery + Solar Panels + Grid + Application Loads ——

EP3300 TLV, split phase inverter, it can support different loads with it’s inbuilt pure copper transformer, like laptop, TV, Air-conditioner, fridge etc... Normally this inverter work with battery as back up system to meet different power demands in daily life; it can also connect extra MPPT/PWM solar charge controller, then work as an solar inverter system, use sunshine energy to save electricity bills.
PRODUCT PARAMETERS
—— Make sure each parameter is true ——
Model |
EP33- 1012 TLV |
EP33- 1024 TLV |
EP33- 1512 TLV |
EP33- 1524 TLV |
EP33- 2012 TLV |
EP33- 2024 TLV |
EP33- 3024 TLV |
EP33- 3048 TLV |
EP33- 4024 TLV |
EP33- 4048 TLV |
EP33- 5048 TLV |
EP33- 6048 TLV |
|||
Inverter Output |
Rated power |
1KW |
1.5KW |
2KW |
3KW |
4KW |
1KW |
1.5KW |
|||||||
Power factor |
1 |
||||||||||||||
Wave form |
Pure sine wave / Same as input wave form (bypass mode) |
||||||||||||||
Output voltage RMS |
110V /120VAC (220V / 230V / 240VAC) |
||||||||||||||
Output frequency |
50Hz or 60Hz (±0.3Hz) (can be set) |
||||||||||||||
Overload protection Output short circuit |
Breraker + software protection |
||||||||||||||
Inverter efficiency (peak) |
>80% |
||||||||||||||
Overload |
100%<Load<110% (alarm 5min then stop output ) / 110%<Load<125% (alarm 60s then stop output) / Load > 125% (alarm 10s then stop output ) |
||||||||||||||
Surge rating |
3000VA |
4500VA |
6000VA |
9000VA |
12000VA |
15000VA |
18000VA |
||||||||
Capable of starting electric motor |
1P |
1P |
1.5P |
1.5P |
2P |
3P |
|||||||||
Battery |
Battery voltage |
12VDC/24VDC |
24VDC/48VDC |
48VDC |
|||||||||||
Minimum start voltage |
11VDC/22VDC/44VDC |
||||||||||||||
Low battery voltage cut off |
(Low voltage fault code04)10/10.5/11V for 12V mode (*2 for 24VDC / *4 for 48VDC) |
||||||||||||||
Low battery voltage alarm |
Add 0.5V / battery:(Low battery alarm one second one time) (10/10.5/11V)+0.5VDC for 12V mode (*2 for 24VDC / *4 for 48VDC) |
||||||||||||||
High battery voltage alarm |
Add 1V/battery:(High battery one second one time /after 30s fault 03) (13.8-14.5V)+1V for 12V mode (*2 for 24VDC/*4 for 48VDC) |
||||||||||||||
Save mode |
Loads ≤ 40W (110V) / 80W (220V) |
||||||||||||||
AC Input Mode |
Input waveform |
Pure sine wave |
|||||||||||||
Nominal input voltage |
220Vac / 230Vac / 240Vac |
||||||||||||||
Max input voltage |
270Vac MAX |
||||||||||||||
Input frequency |
50Hz / 60Hz (auto sensing) |
||||||||||||||
Efficiency (AC mode) |
>95% (load, full battery) |
||||||||||||||
Transfer time AC to DC |
15ms(max) |
||||||||||||||
Charge Mode |
Boost voltage |
14.1V(Default) Range of adjustment 13.8-14.5V / *2 for 24VDC / *4 for 48VDC (Regulation step 0.1V) |
|||||||||||||
Float voltage |
13.5V(Default) Range of adjustment 13.5-13.7V / *2 for 24VDC / *4 for 48VDC (Regulation step 0.1V) |
||||||||||||||
12V |
30A |
45A |
60A |
\ |
\ |
\ |
\ |
||||||||
24V |
20A |
25A |
30A |
40A |
60A |
\ |
\ |
||||||||
48V |
\ |
\ |
\ |
20A |
30A |
35A |
40A |
||||||||
Min charge current 10A. Change by every 5A |
|||||||||||||||
Dimensions |
Dimensions (W*H*D) |
277*196*466mm |
277*186*621mm |
||||||||||||
Ship Dimensions (W*H*D) |
376*306*592mm |
376*296*747mm |
|||||||||||||
Warranty |
One year (standard), 2 years optional (IP20) |